E
THER
CAT S
YSTEM
C
ONFIGURATION
SD4840EK User Manual
ADVANCED MICRO CONTROLS INC.
96
3.2 Add the SD4840EK to the Project (continued)
3.2.3 Configure the SD4840EK
1) Click on the “CoE - Online” tab.
2) Click on the [+] button next to the
6000:0 Index field (Inputs) to expand it.
Note the value of the STATUS_word1
register (6000:01). This value is
typically 0x4408.
3) Click on the [+] button next to the
8010:0 Index field to expand it.
4) The configuration data is available under
the nine sub-index fields of the 8010:0
Index.
Configuration data can be
temporarily changed here.
Double click
on any field to open the
Set Value Dialog
screen to set the parameter to the desired
value. Table R5.3,
found on page 55, allows you to
calculate the proper hexadecimal value
of CFG_word0 for your application.
5) Once you set a parameter, check the
value of the STATUS_word1 register
(6000:01). If the value has bit 13 set to
“1”, there is an error in your
configuration setting. (An example is a
STATUS_word1 register change from
0x4408 to 0x6408.)
6) To make these changes permanent, you
must define values under the “Startup”
tab. Click on the “Startup” tab.
7) Right click on the blank surface and
select “Add New Item...” in the resulting
pop up menu.
8) Click on the [+] button next to the
8010:0 Index field to expand it.
9) Double click on the field that must be
changed. This opens a dialog that will
allow you to set the field with a decimal
or hexadecimal value.
10) Click the [OK] button in the dialog box
to set the new value.
11) Click the [OK] button in the “Edit
CANopen Startup Entry” screen to
accept the new startup parameter
setting.
Figure T3.3 SD4840EK Configuration Registers
Figure T3.4 SD4840EK Configuration Registers
Содержание SD4840EK
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S310...
Страница 6: ...TABLE OF CONTENTS SD4840EK User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 38: ...MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 38 Notes...
Страница 48: ...CALCULATING MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 48 Notes...
Страница 78: ...COMMAND DATA FORMAT SD4840EK User Manual ADVANCED MICRO CONTROLS INC 78 Notes...
Страница 94: ...INSTALLING THE SD4840EK SD4840EK User Manual ADVANCED MICRO CONTROLS INC 94 Notes...
Страница 104: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...