Output Data Format
ADVANCED MICRO CONTROLS INC.
5
60
Command Block 4: Adjust LS Setpoint Positions
This block allows you to incrementally adjust the limit switch setpoint positions to fine tune setpoints during
machine operation.
1) You cannot adjust stitching outputs.
2) It is possible to invert the output by adjusting the From setpoint to a position beyond the To
setpoint or by adjusting the To setpoint to a position before the From setpoint.
3) If multiple setpoint pairs exist on the output and you invert one of them the ANS1 will
respond with an Overlap Error. (See Table 6.2,
, on page 74 for addi-
tional information.)
Figure 5.7 Command Block 4
Command Word Bits
Bits 6-13:
Adjust Setpoint.
When the bit is reset to ‘0’, the corresponding setpoint will not be adjusted.
When the bit is set to ‘1’, the corresponding setpoint will be incremented or decremented by one.
Bit 14: Adjustment Direction.
When this bit is reset to ‘1’ the setpoint position will decrement by one if the
corresponding Adjust Setpoint bit is set to ‘1’. When this bit is set to ‘1’ the setpoint position will
increment by one if the corresponding Adjust Setpoint bit is set.
EtherNet/IP
Address
Modbus
Address
Bit Number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
1024
T
ransmit Bi
t
Adjust Di
rection
Ad
jus
t T
O
-4
Adjus
t FRO
M
-4
Ad
jus
t T
O
-3
Adjus
t FRO
M
-3
Ad
jus
t T
O
-2
Adjus
t FRO
M
-2
Ad
jus
t T
O
-1
Adjus
t FRO
M
-1
0
Clear Error
0
1
0
0
1
1025
Output Point to be adjusted (1 to 16)
2-19
1026-1043
Not Used
Содержание ANS1 ANYNET-I/O
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A090...
Страница 6: ...Table of Contents ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 26: ...Limit Switch Functionality ADVANCED MICRO CONTROLS INC 2 26 Notes...
Страница 36: ...Additional Functionality ADVANCED MICRO CONTROLS INC 3 36 Notes...
Страница 90: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...