20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
Installing the ANS1
4
45
Encoder Wiring (continued)
Single Ended Wiring
Figure 4.8 below shows how to wire the encoder inputs to both a single ended sourcing and single ended sink-
ing encoder outputs.
The encoder inputs on the ANG1 are rated for 5Vdc only. You must use a current limit-
ing resistor on each input if the outputs of your encoder are greater than 5Vdc. Appro-
priate current limiting resistors are shown in the figure below.
Figure 4.8 Single Ended Encoder Wiring
Relay Board Installation
AMCI offers the RB-7 and RB-8 relay boards for connecting outputs 1 through 8 to the outside world.
The RB-7 offers eight solid-state relay outputs
The RB-8 offers eight solid-state relay outputs and eight opto-isolated DC inputs
ANS1 Encoder Input Connection to Sourcing Encoder Output
ANS1 Encoder Input Connection to Sinking Encoder Output
R
LIM
R
LIM
OUT
OUT
–
–
Supply
R
LIM
5 Vdc
None
12 Vdc
2.0 Kohm
15 Vdc
2.4 Kohm
24 Vdc
4.7 Kohm
+
+
–
–