CHAPTER 3. USING DISPLAY SCREENS
CD-A DUAL PULSE RESISTANCE WELDING POWER SUPPLY
990-430
3-9
RESET DEFAULTS
Press the
MENU
button again to select the
RESET
DEFAULTS
. The default selection is
OFF.
To set all schedules, limits, weld counter, weld
counter limits and all menu items back to their
factory default values, select
ON
, then press
SAVE
to save changes.
To discard changes, press
RUN
to activate the
SAVE PROMPT
and at the prompt, press
CLEAR
to
discard changes. After saving or discarding new
settings, the display will revert to the original
screen selected.
REPEAT MODE
Press the
MENU
button again to highlight the
REPEAT MODE
selection. When this is set to
ON
,
the control provides an automatic repeat of the
weld sequence for simple automated air actuated
applications. This weld function is ideal for
volume production which requires a single
schedule.
REPEAT MODE
can
only
be used with an Air
Actuated Weld Head. On Force Fired Air
Actuated Weld Heads, weld current begins when
both levels of a two-level Foot Switch are closed
and held down and then the Force Firing Switch
in the Air-Actuated Weld Head closes sending a
fire signal.
Note: Weld Mode set to FS1+FS2+FSW.
When
REPEAT MODE
is used with a Non-Force Fired Air Actuated Weld Head (Weld Mode set to
FS1+FS2), the Squeeze (SQZ) Period must be used to allow sufficient time for the electrodes to close and
apply the required weld force to the parts
before
the Weld Period begins. Weld current begins when the
Squeeze Period ends and a fire signal is received. During this whole operation
both
levels of a two-level
Foot Switch must remain closed to continue in
REPEAT MODE
.
When
REPEAT MODE
is used with any type of Air Actuated Weld Head, the Hold Period can be used to
automatically keep the electrodes closed on the parts after weld current has terminated to provide
additional heat sinking or parts cooling.
REPEAT TIME
, which is applicable only to
REPEAT MODE
, sets
the cycling rate between welds by controlling how long the electrodes remain open.
When
REPEAT MODE
is set to
ON
, and the user keeps the footswitch depressed and firing switch closed,
the control will repeatedly actuate the weldhead and perform the weld sequence. If set to
ON
, a
REPEAT
TIME
other than
0
must also be set.