CONTROL UNITS СU-TR230 / СU-TR400
106
106
SETTINGS
MENU
SETTING
DESCRIPTION
VALUES
FACTORY
VALUE
P5
F2
*
Sensitivity of obstacle detection when
closing.
When closing, the detection of an
obstacle will cause it to stop and then open
again (opening value is set by
P5
–
F5
no
— disabled
01
,
02
,
03
…
99
:
01
— max.
99
— min.
no.
*
Y
Settings
F1
,
F2
,
F6
(menu
P5
) relate to the operation of the obstacle detection system
integrated in the control unit. The decision about the need to adjust and the settings of
F1
,
F6
(when opening) and
F2
(when closing) are carried out by qualified specialists (EN 12635)
of the competent organization.
The settings can be used for added safety, for example, during door closing additionally to
safety contact edge or, for example, during door opening in case there are apertures over
50 mm or protruding parts in the door leaf that a person can grab or stand on.
In case of use, the settings must ensure the safe and correct operation of the drive system
in accordance with the applicable regulatory documents (EN 12453), excluding damage,
false alarms. After setting, measurements are required according to the methodology of
regulatory documents
F3
Operating time when opening
01
,
02
,
03
…
99
:
01
— 1 s
99
— 99 s
99.
F4
Operating time when closing
Y
In
P5
–
F3
and
P5
–
F4
, the time for continuous movement of doors between the end
positions is set. The operating time should be sufficient to fully open or close (it is
recommended that during setting to set the time more by 3–5 s). If the set operating time
is less than the time required to fully open / close the door, then the movement of the door
leaf stops after the operating time has expired.
F5
Opening time (reverse) after the safety de
vice is activated when closing.
It automatical-
ly opens after activation the inputs
PH1
and
SE
(
Table
2, connector 20), the built-in obstacle
detection system (
P5
–
F2
)
01
— opening
to end position
02
— opening ~2 s
03
— opening ~1 s
01.
F6
**
Sensitivity of obstacle detection at the be
ginning of opening.
The setting allows the
system integrated in the control unit to de-
tect an obstacle at the very beginning of the
opening
no
— disabled
01
,
02
,
03
…
99
:
01
— min.
99
— max.
no.
***
F7
Disabling the safety edge near the floor.
When the setting is actuated, the operation of
the
SE
input (
Table
2, connector 20) near the
floor will be disabled. For drives with switch-
es, the disabling position is set by the switch
of the drive connected to input
5.L
(
Figure
12).
For drives with an encoder, the disabling po-
sition is set by the unit automatically from the
set end position of door closing; position cor-
rection is possible (
P1
–
F6
)
no
— disabled
on
— enabled
no.
* The unit will offer a value (inscription of the value without a dot), from which it is recommended to start setting
and verification.
** Only for control unit CU-TR230.
*** The unit will offer a value (inscription of the value without a dot), from which it is recommended to start setting
and verification.
Содержание CU-TR230
Страница 2: ......
Страница 44: ......
Страница 86: ......
Страница 126: ...Control units СU TR230 СU TR400 124 124 200 310 164 270 R40 90 118 244 271 350 377 2 3 ...
Страница 129: ...Control units СU TR230 СU TR400 127 127 8 14 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 ...
Страница 130: ...Control units СU TR230 СU TR400 128 128 9 14 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 ...
Страница 136: ...Control units СU TR230 СU TR400 134 134 5 L GND P L GND CL L O_S 16 OP L IN_S P1 F0 01 MENU S5 NO CU TR TR COM NC NO 24 ...
Страница 137: ......