As the unit makes the transition from auto to manual (and vice-versa), the
4-20mA goes directly to the value specified by the Modbus register.
Registers 40255-40258 (0-100% output on AO 1-4) may be used to preload a val-
ue into the applicable Auto/Manual register before switching over to manual mode.
26.3
Note 3: Setpoint Class and Time
The highest 2 bits represent the input class (‘00’ – class A, ‘01’ – class B, ‘10’
– class C).
The lower 14 bits represent the time associated with the class (N/A for class A,
seconds for class B, and minutes for class C).
For analog channels, the first register corresponds to the low setpoint input class
and the second register corresponds to the high safety setpoint input class.
For discrete channels, the first register corresponds to the input class and the
second register is N/A.
For example, if Channel 2 is an analog input with a low setpoint class B of 60
seconds and a high setpoint class C of 10 minutes, the registers would hold the
following values:
Register
Value
43175
01000000 00111100
43176
10000000 00001010
26.4
Note 4: Calibration 1
The ZERO and SPAN Modbus registers are used to ‘tweak’ the sensors (typically
pressure) to read a known value.
SPAN – Slope of the line relating the sensor range to the domain. Typical val-
ues would be from 1-255. It is recommended that this value be read and then
changed by one. This value should not be greater than 512.
ZERO – Y-intercept of the line described above. It is recommended that this
value be read and then changed by 13.
MIN/MAX SENSOR LIMIT (Writable) – lowest and highest permissible displayed
values that can be used on a particular channel (must also consider the channel’s
decimal position). These values are signed integers. While this value may be writ-
ten, it is recommended that the PC terminal program perform this function.
26.5
Note 5: Hour/Service Meters
For both the remaining hours and the reset values, each meter uses two regis-
ters to represent the 32-bit integer. The first register is the low word and the
second is the high word. A value of ‘FFFF’ indicates that the meter is unused.
For example, the first two meters’ current hour value would be read as follows,
Register
Description
44609
Hourmeter
high word
44610
low word
44611
Service Meter #1
high word
44612
low word
Содержание DE-3000+ Series
Страница 71: ...DE 3000 IOI 8 15 All rights reserved ALTRONIC LLC 2015 71 FIG 2 DE 3000 SYSTEM DIAGRAM DE 3000 ...
Страница 74: ...DE 3000 IOI 8 15 All rights reserved ALTRONIC LLC 2015 74 FIG 5 WIRING DIAGRAM PERSONAL COMPUTER ...
Страница 75: ...DE 3000 IOI 8 15 All rights reserved ALTRONIC LLC 2015 75 FIG 6 WIRING DIAGRAM SENSOR AND TRANSDUCER INPUTS ...
Страница 76: ...DE 3000 IOI 8 15 All rights reserved ALTRONIC LLC 2015 76 FIG 7 WIRING DIAGRAM CURRENT LOOP OUTPUTS ...
Страница 77: ...DE 3000 IOI 8 15 All rights reserved ALTRONIC LLC 2015 77 FIG 8 WIRING DIAGRAM DIGITAL OUTPUT SWITCHES ...