Troubleshooting
Appendix
E
0xF0878
Recoverable An index used to access a bit is beyond the
boundaries of the data type it is used on.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 313
.
2. Correct the program to ensure that there is no index used to access
a bit beyond the boundaries of the data type.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF880
Recoverable A data conversion error occurred.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 313
.
2. Correct the program to ensure that there is no data conversion error.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF888
Recoverable The call stack of the controller cannot support the
sequence of calls to function blocks in the current
project. Too many blocks are within another
block.
Perform the following:
•
See
Corrective Actions for Recoverable Faults on page 313
.
•
Change the project to reduce the quantity of blocks being called
within a block.
0xF898
Recoverable An error occurred in the user interrupt
configuration for the plug-in I/O module.
Perform the following:
•
See
Corrective Actions for Recoverable Faults on page 313
.
•
Correct the user interrupt configuration for plug-in I/O module in the
user program to match that of the actual hardware configuration.
0xF8A0
Recoverable The TOW parameters are invalid.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 313
.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
0xF8A1
Recoverable The DOY parameters are invalid.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 313
.
2. Correct the program to ensure that there are no invalid parameters.
3. Build and download the program using Connected Components
Workbench.
4. Put the Micro800 controller into Run mode.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...