Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
113
Motion Control
Chapter
7
Motor and Load Parameters
Parameter
Description and Values
User-defined unit
Defines user unit scaling that matches your mechanical system values.
These units shall be carried forward into all command and monitor axis in
user unit values throughout programming, configuration and monitoring
functions.
Position
Select from any of the following options:
–
mm
–
cm
–
inches
–
revs
–
custom unit (ASCII format of up to 7 characters long)
Time
Read only. Predefined in seconds.
Motor revolution
Defines pulse per revolution and travel per revolution values.
Pulse per revolution
(1)
(1)
The parameter is set as REAL (float) value in Connected Components Workbench. To learn more about
conversions and rounding of REAL values, see
Real Data Resolution on page 118
Defines the number of pulses needed to obtain one revolution of the
drive motor.
Range
: 0.0001…8388607
Default
: 200.0
Travel per revolution
(1)
Travel per revolution defines the distance, either linear or rotational, that
the load moves per revolution of the motor.
Range
: 0.0001…8388607.
Default
:1.0 user unit.
Direction
Defines polarity, mode, and change of delay time values.
Polarity
Direction polarity determines whether the direction signal received by
the controller as a discrete input should be interpreted on the input as
received by the motion controller, (that is, the non-inverted case), or
whether the signal should be inverted prior to interpretation by the
motion control logic.
Set as Inverted or Non-inverted (default).
Mode
Set as Bi-directional (default), Positive (clockwise), or Negative
(counter-clockwise) direction.
Change delay time
Configure from 0…100 ms.
Default value is 10 ms.
TIP
A red border on an input field indicates that an invalid value has been
entered. Scroll over the field to see tooltip message that will let you
know the valid value range for the parameter. Supply the valid value.
ATTENTION:
Modifying Motor Revolution parameters may cause
axis runaway.
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...