![Allen-Bradley Micro830 Скачать руководство пользователя страница 226](http://html.mh-extra.com/html/allen-bradley/micro830/micro830_manual_2900197226.webp)
212
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Appendix A
Specifications
Micro830 16-Point Controllers
General Specifications
Attribute
2080-LC30-16AWB
2080-LC30-16QWB
2080-LC30-16QVB
Number of I/O
16 (10 inputs, 6 outputs)
Dimensions (HxWxD)
90 x 100 x 80 mm (3.54 x 3.94 x 3.15 in.)
Shipping weight, approx.
0.302 kg (0.666 lb)
Wire size
0.14…2.5 mm
2
(26…14 AWG) solid copper wire or
0.14…1.5 mm
2
(26…16 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
Wire type
Use Copper Conductors only
Terminal screw torque, max
0.6 Nm (4.4 lb-in.)
(using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Input circuit type
120V AC
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type
Relay
12/24V DC sink transistor (standard
and high-speed)
Event input interrupt support
Yes
Power consumption, max
5 W – without plug-in modules
7.88 W – with plug-in modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
120V AC, 16 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
24V DC, 1 A per point
(Surrounding air temperature 30 °C)
24V DC, 0.3 A per point
(Surrounding air temperature 65 °C)
Isolation voltage
250V (continuous), Reinforced
Insulation Type, Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 3250V DC I/O
to Aux and Network, Inputs to Outputs
250V (continuous), Reinforced
Insulation Type, Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, Inputs
to Aux and Network, 3250V DC
Outputs to Aux and Network, Inputs to
Outputs
50V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60s @ 720 V DC, I/O to
Aux and Network, Inputs to Outputs
Pilot duty rating
C300, R150
–
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...