Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
213
Specifications
Appendix
A
Inputs
Attribute
2080-LC30-16AWB
2080-LC30-16QVB, 2080-LC30-16QWB
120V AC Input
High-Speed DC Input
(Inputs 0…3)
Standard DC Input
(Inputs 4…9)
Number of Inputs
10
4
6
Input group to backplane
isolation
Verified by the following dielectric
tests: 1,400V AC for 2 s
132V working voltage (IEC Class 2
reinforced insulation)
Verified by the following dielectric tests: 1,414V DC for 2 s
75V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
110V AC
24V DC sink/source
On-state voltage range
79…132V AC
47…63 Hz
16.8…26.4V DC
10…26.4V DC
Off-state voltage, max
20V AC
5V DC
Off-state current, max
1.5 mA
On-state current, min
5 mA @ 79V AC
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
12 mA @ 120V AC
7.66 mA @ 24V
6.15 mA @ 24V
On-state current, max
16 mA @ 132V AC
12.0 mA @ 30V DC
Nominal impedance
12 k
Ω
@ 50 Hz
10 k
Ω
@ 60 Hz
3 k
Ω
3.74 k
Ω
Inrush current, max
250 mA @ 120V AC
—
Turn on time/
Turn off time, max
(without filtering)
ON: 1 ms
OFF: 8 ms
ON: 3.2
µ
s
OFF: 0.6
µ
s
ON: 33
µ
s…0.1 ms
OFF: 22
µ
s…0.02 ms
IEC input compatibility
Type 3
AC input filter setting
8 ms for all embedded inputs
(In Connected Components Workbench, go to the Embedded I/O configuration window to reconfigure the filter setting for
each input group)
Isolated AC Inputs
Attribute
2080-LC30-16QWB, 2080-LC30-16QVB
(Inputs 0…3)
On-state voltage, nom
12/24V AC @ 50/60 Hz
Off-state voltage, min
4V AC @ 50/60 Hz
Operating frequency, nom
50/60 Hz
Outputs
Attribute
2080-LC30-16AWB,
2080-LC30-16QWB
2080-LC30-16QVB
Relay Output
Hi-Speed Output
(Outputs 0…1)
Standard Output
(Outputs 2…5)
Number of outputs
6
2
4
Output voltage, min
5V DC, 5V AC
10.8V DC
10V DC
Output voltage, max
125V DC, 265V AC
26.4V DC
26.4V DC
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...