Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
215
Specifications
Appendix
A
Input circuit type
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type
Relay
24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Event input interrupt support
Yes
Power consumption, max
8 W – without plug-in modules
12.32 W – with plug-in modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
24V DC, 8.8 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
24V DC, Class 2, 1 A per point (Surrounding air temperature 30 °C)
24 V DC, Class 2, 0.3 A per point (Surrounding air temperature 65 °C)
Isolation voltage
250V (continuous), Reinforced
Insulation Type, Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, Inputs
to Aux and Network, 3250 V DC
Outputs to Aux and Network, Inputs to
Outputs
50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to
Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs
Pilot duty rating
C300, R150 (2080-LC30-24QWB only)
—
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
.
General Specifications
Attribute
2080-LC30-24QWB
2080-LC30-24QVB
2080-LC30-24QBB
Inputs
Attribute
2080-LC30-24QWB, 2080-LC30-24QVB, 2080-LC30-24QBB
High-Speed DC Input
(Inputs 0…7)
Standard DC Input
(Inputs 8 and higher)
Number of Inputs
8
6
Voltage category
24V DC sink/source
Operating voltage range
16.8…26.4V DC
10…26.4V DC
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state current, min
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
8.8 mA @ 24V DC
8.5 mA @ 24V DC
On-state current, max
12.0 mA @ 30V DC
Nominal impedance
3 k
Ω
3.74 k
Ω
IEC input compatibility
Type 3
AC input filter setting
8 ms for all embedded inputs
(In Connected Components Workbench software, go to the
Embedded I/O configuration window to re-configure the filter
setting for each input group)
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...