![Allen-Bradley Micro830 Скачать руководство пользователя страница 200](http://html.mh-extra.com/html/allen-bradley/micro830/micro830_manual_2900197200.webp)
186
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Chapter 10
Using microSD Cards
The ConfigMeFirst.txt file must be placed in the same root directory as the
backup folder in the microSD card.
1.
Insert the microSD card into the microSD card slot.
2.
Cycle power to the controller.
3.
When the SD LED displays a steady green light, the project restore is
complete.
Data Log
The data logging feature allows you to capture global and local variables with
timestamp from the Micro800 controller into the microSD card. You can retrieve
the recorded datasets on the microSD card by reading the contents of the
microSD card through a card reader or by doing an upload through the
Connected Components Workbench software.
A maximum number of 10 datasets is supported for a Micro800 program. Each
dataset can contain up to 128 variables, with a maximum of four (4) data string
variables per dataset. String variables can have a maximum of 252 characters. All
datasets are written to the same file. For more information on how data logs are
stored on the microSD card, see the
Data Log Directory Structure on page 187
.
You can retrieve data log files from the microSD card using a card reader or by
uploading the data logs through Connected Components Workbench.
See the sample quickstart project to get you started on the Data Log feature,
the Data Log Feature on page 196
IMPORTANT
Uploading data log files in PROGRAM mode is recommended for
optimum performance and to prevent file access conflict. For example, if
the data log instruction is executing, Connected Components Workbench
will not upload the last data log file.
IMPORTANT
Data log execution time depends on the user application and its
complexity. Users are advised to data log
no faster than every two
seconds
for typical applications. Note that housekeeping takes at least
5 ms per program scan. See
Program Execution in Micro800 on page 75
for more information on program scan and execution rules and sequence.
See also
Data Log – Data Payload vs. Performance Time on page 237
IMPORTANT
Note that in cases where there are simultaneous RCP and DLG function
block execution or uploads/downloads/searches, the activities are
queued up and handled one by one by the program scan. Users will
notice a slowdown in performance in these cases.
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...