126
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Chapter 7
Motion Control
1.
Moving part moves to its right side (in positive direction) in creep velocity
to detect Lower Limit switch On
→
Off edge;
2.
Once Lower Limit switch On
→
Off edge is detected, record the position
as mechanical home position, and decelerate to stop;
3.
Move to the configured home position. The mechanical home position
recorded during moving right sequence, plus the home offset configured
for the axis through the software.
Scenario 3: Moving part at left (negative) side of Lower Limit switch before
homing starts
In this case, the homing motion fails and moves continuously to the left until
drive or moving part fails to move. User needs to make sure the moving part is at
the proper location before homing starts.
MC_HOME_REF_WITH_ABS
MC_HOME_REF_WITH_ABS (2) homing procedure performs a homing
operation against Home switch, plus fine Ref Pulse signal. The actual motion
sequence is dependent on the home switch, limit switch configuration, and the
actual status for the switches before homing starts—that is, when the MC_Home
function block is issued.
Scenario 1: Moving part at right (positive) side of Home switch before homing
starts
The homing motion sequence for this scenario is as follows:
1.
Moving part moves to its left side (in negative direction);
2.
When Home Abs switch is detected, the moving part decelerates to stop;
3.
Moving part moves back (in positive direction) in creep velocity to detect
Home Abs On
→
Off edge;
4.
Once Home Abs switch On
→
Off is detected, start to detect first Ref
Pulse signal coming in;
5.
Once the first Ref Pulse signal comes, record the position as mechanical
home position, and decelerate to stop;
6.
Move to the configured home position. The mechanical home position
recorded during moving back sequence, plus the home offset configured
for the axis through the Connected Components Workbench software.
IMPORTANT
If Home switch or Ref Pulse is not configured as Enabled,
MC_HOME_REF_WITH_ABS (2) homing fails with Error ID:
MC_FB_ERR_PARAM.
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...