Publication 1769-UM005A-EN-P
Module Data, Status, and Channel Configuration
4-5
Configuring Channels
After module installation, you must configure operation details, such as
RTD type, temperature units, etc., for each channel. Channel
configuration data for the module is stored in the controller configuration
file, which is both readable and writable.
Configuration Data File
The configuration data file is shown below. Bit definitions are provided in
Channel Configuration on page 4-6. Detailed definitions of each of the
configuration parameters follows the table.
The default configuration of the table is all zeros, which yields the
following.
NOTE
Normal channel configuration is done using
programming software. In that case, it is not necessary to
know the meaning of the bit location. However, some
systems allow configuration to be changed by the control
program. Refer to your controller’s documentation for
details.
Table 4.2 Default Configuration
Parameter
Default Setting
Channel Enable/Disable
Disable
Data Format
Raw/Proportional
Input/Sensor Type
100
Ω
Platinum 385
Temperature Units/Mode
°C (not applicable with Raw/Proportional)
Open/Broken Circuit Response
Upscale
Cyclic Lead Compensation
Enable
Excitation Current
1.0 mA
Input FIlter Frequency
60 Hz
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...