Publication 1769-UM005A-EN-P
Installation and Wiring
3-15
2-Wire Potentiometer Interconnection
3-Wire Potentiometer Interconnection
EXC 3
SENSE 3
RTN 3
EXC 3
SENSE 3
RTN 3
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Add Jumper
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Add Jumper
Belden 9501 Shielded Cable
Belden 9501 Shielded Cable
NOTE
The potentiometer wiper arm can be connected to
either the EXC or return terminal depending on
whether you want increasing or decreasing resistance.
EXC 3
SENSE 3
RTN 3
EXC 3
SENSE 3
RTN 3
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Sense
Run RTD and sense wires from the module to
potentiometer terminal and tie terminal to one point.
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Sense
Run RTD and sense wires from the module to
potentiometer terminal and tie terminal to one point.
NOTE
The potentiometer wiper arm can be connected to either
the EXC or return terminal depending on whether you
want increasing or decreasing resistance.
Belden 83503 or 9533 Shielded Cable
Belden 83503 or 9533 Shielded Cable
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...