Chapter
4
Module Data, Status, and Channel Configuration
After installation of the 1769-IR6 RTD/resistance input module, you must
configure it for operation, usually using the programming software
compatible with the controller (for example, RSLogix 500™ or
RSLogix 5000™). Once configuration is complete and reflected in ladder
logic, you will need to get the module up and running and then verify its
operation. This chapter includes information on the following:
•
module memory map
•
accessing input image file data
•
configuring channels
•
configuring periodic calibration
•
preparing ladder logic to reflect the configuration
•
running the module
•
verifying the configuration
Module Memory Map
The module uses eight input words for data and status bits (input image),
and seven configuration words.
Channel 0 Data Word
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
General/Open-Circuit Status Bits
Over-/Under-range Bits
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
Word 0
Word 1
Word 2
Word 3
Input Image
8 words
Configuration
File
7 words
slot e
slot e
Input Image
File
Configuration
File
Memory Map
Bit 15
Bit 0
Channel 4 Data Word
Channel 5 Data Word
Word 6
Word 7
Channel 4 Configuration Word
Channel 5 Configuration Word
Word 4
Word 5
Module Configuration Word
Word 6
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...