Publication 1769-UM005A-EN-P
Installation and Wiring
3-11
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1.
Loosen the terminal screws to be wired.
2.
Route the wire under the terminal pressure plate. You can use
the bare wire or a spade lug. The terminals accept a 6.35 mm (0.25
in.) spade lug.
3.
Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is
0.68 Nm (6 in-lbs).
NOTE
If you need to remove the finger-safe cover, insert a
screwdriver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be able
to put it back on the terminal block because the wires
will be in the way.
NOTE
The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [maximum 1/4 inch o.d. with
a 0.139 inch minimum i.d. (M3.5)] with the module.
wiring the
finger-safe
terminal block
upper retaining screw
lower retaining screw
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...