Publication 1769-UM005A-EN-P
Installation and Wiring
3-13
3.
At the module end of the cable, twist the drain wire and foil shield
together, bend them away from the cable, and apply shrink wrap.
Then earth ground via a panel or DIN rail mounting screw at the end
of the module. Keep the length of the drain wire as short at possible.
4.
At the other end of the cable, cut the drain wire and foil shield back to
the cable and apply shrink wrap.
5.
Connect the signal wires to the terminal block as described for each
type of input. See Wiring RTDs on page 3-13 or Wiring Resistance
Devices (Potentiometers) on page 3-14.
6.
Connect the other end of the cable to the analog input device.
7.
Repeat steps 1 through 6 for each channel on the module.
Wiring RTDs
Three types of RTDs can be connected to the 1769-IR6 module:
•
2-wire RTD, which is composed of an RTD EXC (excitation) lead wire
and a RTN (return) lead wire
•
3-wire RTD, which is composed of a Sense and 2 RTD lead wires
(RTD EXC and RTN)
•
4-wire RTD, which is composed of a Sense and 2 RTD lead wires
(RTD EXC and RTN). The second sense wire from the 4-wire RTD is
left open.
ATTENTION
!
Be careful when stripping wires. Wire fragments that fall
into a module could cause damage at power up.
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...