Publication 1769-UM005A-EN-P
3-14
Installation and Wiring
2-Wire RTD Configuration
3-Wire RTD Configuration
4-Wire RTD Configuration
Wiring Resistance Devices (Potentiometers)
Potentiometer wiring requires the same type of cable as that for the RTDs
described on page 3-9. Potentiometers can be connected to the module as
a 2-wire or 3-wire connection as shown on page 3-15.
EXC 3
SENSE 3
RTN 3
EXC 4
Belden 9501 Shielded Cable
Cable Shield (to Ground)
RTD EXC
Return
RTD EXC
Return
Add Jumper
EXC 3
SENSE 3
RTN 3
EXC 4
Belden 83503 or 9533 Shielded Cable
Cable Shield (to Ground)
RTD EXC
Sense
RTD EXC
Return
Sense
Return
EXC 3
SENSE 3
RTN 3
EXC 4
Belden 83503 or 9533 Shielded Cable
Leave one sensor wire open.
Cable Shield (to Ground)
RTD EXC
Return
RTD EXC
Return
Sense
Sense
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...