Publication 1769-UM005A-EN-P
4-6
Module Data, Status, and Channel Configuration
The following table shows the basic arrangement of the configuration data
file.
Channel Configuration
Words 0 to 5 of the configuration file allow you to change the parameters
of each channel independently. For example, word 0 corresponds to
channel 0, word 1 to channel 1, etc. The functional arrangement of the
bits for one word is shown in the table on page 4-7.
Table 4.3 Configuration Data File
Word/
Bit
15
14 13 12
11
10
9
8
7
6
5
4
3
2 1
0
0
Enable/
Disable
Channel 0
Data Format
Channel 0
Input/Sensor Type
Channel 0
Temperature
Units/Mode
Channel 0
Open/Broken
Circuit
Response
Channel 0
Cyclic Lead
Compensation
Channel 0
Excitation
Current
Channel 0
Filter Frequency
Channel 0
1
Enable/
Disable
Channel 1
Data Format
Channel 1
Input/Sensor Type
Channel 1
Temperature
Units/Mode
Channel 1
Open/Broken
Circuit
Response
Channel 1
Cyclic Lead
Compensation
Channel 1
Excitation
Current
Channel 1
Filter Frequency
Channel 1
2
Enable/
Disable
Channel 2
Data Format
Channel 2
Input/Sensor Type
Channel 2
Temperature
Units/Mode
Channel 2
Open/Broken
Circuit
Response
Channel 2
Cyclic Lead
Compensation
Channel 2
Excitation
Current
Channel 2
Filter Frequency
Channel 2
3
Enable/
Disable
Channel 3
Data Format
Channel 3
Input/Sensor Type
Channel 3
Temperature
Units/Mode
Channel 3
Open/Broken
Circuit
Response
Channel 3
Cyclic Lead
Compensation
Channel 3
Excitation
Current
Channel 3
Filter Frequency
Channel 3
4
Enable/
Disable
Channel 4
Data Format
Channel 4
Input/Sensor Type
Channel 4
Temperature
Units/Mode
Channel 4
Open/Broken
Circuit
Response
Channel 4
Cyclic Lead
Compensation
Channel 4
Excitation
Current
Channel 4
Filter Frequency
Channel 4
5
Enable/
Disable
Channel 5
Data Format
Channel 5
Input/Sensor Type
Channel 5
Temperature
Units/Mode
Channel 5
Open/Broken
Circuit
Response
Channel 5
Cyclic Lead
Compensation
Channel 5
Excitation
Current
Channel 5
Filter Frequency
Channel 5
6
Not Used
Enable/
Disable Cyclic
Calibration
(1)
(1) When enabled, an autocalibration cycle is performed on all enabled channels every 5 minutes.
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...