Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 4
Output Module Features
Short Circuit Protection with Safety Output Modules
describes what happens when a short circuit
condition is detected
on
a Compact 5000 I/O safety output module.
describes what happens when the short circuit condition is removed
from a Compact 5000 I/O safety output module and the data is set to safe
state, that is, the off state.
For more information on the maximum current that you can apply to an
output, see the Compact 5000 I/O Modules and EtherNet/IP Adapters
Technical Data, publication
Table 30 - Short Circuit Protection - Compact 5000 I/O Safety Output Modules
Output Behavior
Tag Value
Diagnostic Value
I/O Status Indicator
State
• Faults
• Turns off
One of the following:
• If the output point is
shorted to 24V DC, the
I.Ptxx.ShortCircuit
tag = 1.
• If the output point is
shorted to ground, no tags
are changed.
One of the following:
• If the output point was
shorted to 24V DC when
the short circuit condition
was detected, the Short
Circuit diagnostic = 1.
• If the output point is
shorted to ground when
the short circuit condition
was detected, the Short
Circuit to Ground
diagnostic = 1.
One of the following:
• Flashes red if the
output point is
shorted to 24V DC.
• Off if the output
point is shorted to
ground.
Table 31 - Short Circuit Protection - Compact 5000 I/O Safety Output Modules
Output Behavior
Tag Value
Diagnostic Value
I/O Status Indicator
State
Restarts in its
commanded state
One of the following:
• If the output point is
shorted to 24V DC, the
I.Ptxx.ShortCircuit
tag = 0.
• If the output point is
shorted to ground, no tags
are changed.
One of the following:
• If the output point was
shorted to 24V DC when
the short circuit condition
was detected, the Short
Circuit diagnostic = 0.
IMPORTANT
: You must
cycle power to the module
to reset the diagnostic.
• If the output point is
shorted to ground when
the short circuit condition
was detected, the Short
Circuit to Ground
diagnostic = 0.
Turns off if there is no
longer a load that is
connected to the
output.
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......