248
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix B
Module Tag Definitions
Ptxx.InputOnOffFilter
SINT
The amount of time that a signal must be in the off state
before the input data indicates the off state. The amount
of time is indicated using an enumeration. Not all
products support all enumeration values.
• 5 = 0 μs
• 6 = 5 μs
• 7 = 10 μs
• 8 = 20 μs
• 9 = 50 μs
• 10 = 100 μs
• 11 = 200 μs
• 12 = 500 μs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
Ptxx.ChatterTime
INT
A value from 1…10000 ms in whole ms increments.
1…10000
Ptxx.ChatterCount
SINT
The number of input changes that are considered Chatter.
• 0 = Disabled
• 2…127 = Enabled
Ptxx.CaptureOffOnEn
BOOL
Enables capturing Off to On time stamps. If cleared, point
does not record Off to On time stamps.
• 0 = Capture disabled (default) for OFF to ON
input transitions
• 1 = Capture enabled for OFF to ON input
transitions
Ptxx.CaptureOnOffEn
BOOL
Enables capturing On to Off time stamps. If cleared, point
does not record On to Off time stamps.
• 0 = Capture disabled (default) for ON to OFF
input transitions
• 1 = Capture enabled for ON to OFF input
transitions
Ptxx.TimestampLatchEn
BOOL
When this bit is set, timestamps are latched; this means
that a Timestamp is not overwritten until acknowledged.
All subsequent transitions on that point are ignored until
acknowledged/reset. If the bit is not set, the new LO
Timestamp overwrites the first LO Timestamp
immediately, even if the controller has yet to extract that
data.
The timestamp can also be acknowledge if the
Ptxx.TimestampxxxxxNumber input tag value is written to
the Ptxx.TimestampxxxxxNumberAck output tag value.
It is worth noting that writing the input tag value to the
output tag value, clears the Ptxx.Timestampxxxxx input
tag value.
(1)
• 0 = Timestamps are overwritten with each
successive COS transition.
• 1 = Timestamps are latched until
acknowledged.
(1) In this case, the xxxxx in the tag names represents OffOn or OnOff tags based on what transition occurred. That is, a change in state from Off to On or On to Off.
Table 69 - 5069-IB6F-3W Configuration Tags
Name
Size
Definition
Valid Values
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......