118
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 4
Output Module Features
Output Recovery After Overload or Short Circuit to
Ground Condition
Table 33
describes test output recovery after overload or short circuit to ground
conditions occur.
Thermal Shutoff
Thermal Shutoff helps prevent damage to the output that can result when an
output gets hotter than it can handle.
This feature is
directly related to Short Circuit Protection
feature. The
increased temperature at the output results from an excessive load at the
output. That is, a load with high current is applied to the output. The high
current heats the output beyond an acceptable temperature and the output
turns off.
Table 33 - Output Recovery - Compact 5000 I/O Safety Output Modules
Cause of Fault
Module Operating Conditions
Correction
Recovery Time
Overload Condition
• Output Point Mode - Safety or Safety
Pulse Test.
• Output Data tag = 1.
• Overload current ≥ 1.5 A
Remove the load from the output point.
After the condition is corrected, and the output
is returned to the safe state, it recovers in
whichever of the following times is higher:
• 10 seconds
• Output Error Latch Time - This time is set on
the Points category of the Module
Properties dialog box.
To see where to set the Output Error Latch
Time, go to
.
Short Circuit to Ground
Condition
• Output Point Mode - Safety or Safety
Pulse Test.
• Output Data tag = 1.
• Output is connected directly to ground.
Remove the output connection to ground and
set the output to a safe state.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S
5069-IB8S
OUTPUT
OUTPUT
SA P
ow
er
MOD P
ow
er
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
SA P
ow
er
MOD P
ow
er
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
Standard Modules
Safety Modules
™
NET B1
LINK B1
NET A1
LINK A1
NET A2
LINK A2
SPEED X1
LINK X1
OK
RUN
FORCE
FAN 1
SD
FAN 2
Compact
Logix
5480
B1
A1
1
2
A2
5069-L46ERMW
CONTROLLER
UPS
MP
SA
R
B
F
R
B
F
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
IMPORTANT
The following Compact 5000 I/O digital output modules support the
Thermal Shutoff feature:
• 5069-OB8
• 5069-OB16
• 5069-OB16F
• 5069-OB16K
• 5069-OBV8S
• 5069-OBV8SK
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......