Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
253
Module Tag Definitions
Appendix B
Counterxx.Done
BOOL
Indicates that the I:Count tag ≥ O:Preset.G430.
0 or 1
Counterxx.Rollover
BOOL
The counter counted up to RolloverValue - 1 (for HSC) or
Preset -1 (for simple counters) and then continued
counting from the O:Rollunder (for HSC) or 0 (for simple
counters). The O:RolloverAck bit transitioning from 0 to 1
or the O:Reset transitioning from 0 to 1 clears the bit.
0 or 1
Counterxx.Count
DINT
The number of input transitions counted by a counter.
All values.
EventStatusx.CIPSyncTimeout
BOOL
Indicates that the module was once synced with a 1588
master, but is not now due to a timeout.
• 0 = A valid time master has not timed out.
• 1 = A valid time master was detected on the
backplane, but the time master has timed out.
The module is using its local clock and can be
drifting away from the last known time
master.
EventStatusx.CIPSyncValid
BOOL
Indicates whether the module is synced with a 1588
master.
• 0 = CIP Sync is not available
• 1 = CIP Sync is available
EventStatusx.EventDropped
BOOL
Indicates when an event has been discarded because
events are occurring faster than they are being
acknowledged.
• 0 = An event status has not been dropped
• 1 = An event status has been dropped
EventStatusx.EventNumber
DINT
Running count of events, which increments by one each
new time event. The originator sets the Event Number Ack
to the Event Number to acknowledge receipt of the event.
When the EventNumber reaches it maximum value and
rolls over it is to roll over to 1, not 0.
All values.
EventStatusx.EventReset
BOOL
When EO.Event[<n>].ResetEvent transitions from 0 to 1,
I.EventStatus[<n>].EventReset transitions to 1 to indicate
that the reset was received and completed. It stays 1 until
EO.Event[<n>].ResetEvent transition to zero.
• 0 = Do not reset
• 1 = Reset
EventStatusx.EventsPending
SINT
The number of events currently queued in the modules. A
value greater than zero indicates that the controller is not
currently keeping up with the rate of events.
All positive values.
Ptxx.Data
BOOL
Indicates the current input value.
• 0 = Off
• 1 = On
Ptxx.Fault
BOOL
Indicates that channel data is inaccurate and
cannot be
trusted
for use in the application.
For more information, see
• 0 = Good data
• 1 = Bad data (Faulted)
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Ptxx.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the
degree of inaccuracy is not known
.
For more information, see
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Table 72 - 5069-IB6F-3W Module Input Tags
Name
Size
Definition
Valid Values
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......