276
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix C
Application and Wiring Examples for Safety Modules
When the module is wired as shown, and the requirements listed are met in the
project of the safety controller, it is suitable for applications that are rated up
to, and including,
Category 3
as defined in ISO 13849-1.
To achieve that suitability rating, you must perform diagnostic testing of the
safety function. Configure the safety input channel for Safety Pulse Test to test
the circuit for short circuits to 24V DC.
5069-IB8S
Safety Input 0
Safety Input 1
Safety Input 2
Safety Input 3
Safety Input 4
Safety Input 5
Safety Input 6
Safety Input 7
Test Output 0
Test Output 0
Test Output 1
Test Output 1
Test Output/Muting Output 2
Test Output/Muting Output 2
Test Output/Muting Output 3
Test Output/Muting Output 3
COM
COM
Channel Connections
The diagram shows devices that are connected to
safety input channel 3 and test output channel 0. You
are not restricted to using only those channels.
You can connect devices to any safety input channel
or combination of channels as needed.
We recommend that you connect even-numbered
input points to even-numbered test output points
and odd-numbered input points to odd-numbered
test output points.
This wiring practice can maximize diagnostic
independence and separation.
SA Power
Connections to an external power supply that
provides SA power via the SA Power RTB on one of the
following:
• Compact GuardLogix 5380 controller
• 5069-AENTR or 5069-AEN2TR EtherNet/IP Adapter
• 5069-FPD field potential distributor
IMPORTANT
: Remember the following:
• The 5069-IB8S and 5069-IB8SK modules use DC
SA power. You must connect DC power to the
component, that is, controller, adapter, or field
potential distributor, that provides SA Power to
the modules.
• If you install modules in a system that use AC SA
power and DC SA power, you must install them on
separate SA power buses.
• You use a 5069-FPD field potential distributor to
establish a new SA Power bus in a system. SA
Power buses are isolated from each other. To keep
the modules on separate SA Power buses,
complete the following steps.
1. Install the modules that use one type of SA
power, for example DC, to the right of the
adapter or controller, that is, the first SA
Power bus.
2. Install the 5069-FPD field potential distributor
to establish a second SA Power bus.
3. Install the modules that use the other type of
SA power, for example AC, on the second SA
Power bus.
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......