3
SECTION 3 – FEATURES
3 – FEATURES
3.1 – USER SETUP MENU
The microprocessor program cont
a
ins a User Setup menu system for setting user selectable p
a
rameters. Four
pushbuttons, allow the user access to the menu for setting configuration modes and values. Refer
to the Configuration Programming (Section 5.6) instructions for operation det
a
ils. Also contained in the User Setup
menu is all input and output calibration.
T
he calibration method is completely digital and cont
a
ins no analog
potentiometer adjustment
s
which are susceptible to drif
t.
Non-volatile memory is used for storing all setup p
ar
ameters
and calibration values, and will remain unchanged af
t
er set, even when power to the unit is of
f
.
3.2 – TRANSMITTER HOLD
Certain operations performed by the microprocessor place the unit into a
Ho
ld
mode. This occurs when the User
Setup menu system is activated or when an
A
UTO-zero is performed. When in
Hold
, all
Normal
mode processing is
halted and the output is held at its last value prior to
Hold
.
Normal
operation is indicated by the "CPU Activated"
(dot) in the lower le
f
t of the display blinking at a rate of four times per second.
A
Hold
mode is indicated by the "CPU
Activated"
(dot) blinking at a rate of once per second.
3.3 – AUTOMATIC ZEROING
At periodic intervals the microprocessor will automatically execute an AUTO-zero cycle consisting of the following
sequence: The transmitter output and display signals are put on
Hold
; a valve is activated which disconnect
s
the
process high pressure from the high port of the transducer and connect
s
the process static pressure to both sides of
the transducer, creating a true zero differential pressure; after a brief st
a
bilization period, the transducer zero offset
signal is measured and stored in memory; the valve is deactivated and af
ter
a brief period for process signal st
ab
ilization,
the
Hold
is released and
Normal
process measurement resumes. will be displayed whenever
AUTO
-
zero cycle is in progress.
During
Normal
operation, the zero of
fs
et value stored in memory is subtracted from subsequent transducer readings
until the next
A
UTO-zero cycle occurs and repeat
s
the process. For calibration purposes a switch is provided which
allows the user to manually activate the zeroing valve
.
AUTO-zero On/Off and Interval are available and configurable
using the User Setup menu.
3.4 – DATA DISPLAY
The large integral display is a backlit graphical LCD that displays the current measured process, and is used during
configuration.
3.5 – HIGH TURNDOWN RATIO OPERATION
The VELTRON DPT 2500-
plus
transmitter, with it
s
high level of accuracy and automatic zeroing circuitry
, c
an maintain
linear output signals on applications requiring velocity turndown of 10 to 1 (equal to a velocity pressure turndown of
100 to 1).
3.6 – ENCLOSURE
The VELTRON DPT 2500-
plus
transmitter is packaged in a NEMA
Ty
pe 1 enclosure with standard industrial process
connections. A NEMA Type 12 enclosure is optionally available.
3.7 – MULTIPLE OPERATING POWER SELECTIONS
The VELTRON DPT 2500-
plus
can be powered by 24VAC or 24VDC.
auto zero