This section will detail step
s
necessary to calibrate the VE
LT
RON DPT 2500-
plus
. Calibration is accomplished using
the four programming push buttons det
a
iled in Section 5.
This section can be accomplished with the VELTRON DPT 2500-
plus
mounted in its operating location or at a test
bench in a calibration lab.
If calibrated at a test bench, the VE
LT
RON DPT 2500-
plus
should be positioned in the same attitude as in it
s
operat-
ing location.
6.1 – REQUIRED EQUIPMENT
1. Digital Manometer capable of reading to the nearest 0.001" w.
.
c.
2. Digital Multimeter.
3. Source of clean, dry instrument air.
4. Adjustable low pressure regulator, such as AMC "Low Pressure Air Source" or equal.
6.2 – PREPARATION
1. Turn Power to the VELTRON DPT 2500-
plus
OFF.
2. Remove or open cover of the VELTRON DPT 2500-
plus.
3. Slide switch "AZ Valve" to the ON position (see Figure 4.2).
4. Remove Low and High pressure signal lines to the VELTRON DPT 2500-
plus
.
5. Remove all wires connected to out
p
ut terminals OUT and COM.
6. Turn Power ON.