SECTION 6 – CALIBRATION
23
6.3 – TRANSMITTER INPUT CALIBRATION
6.3.1
For Units With Positive or Negative Differential Pressure Spans.
Zero pressure and transducer natural sp
a
n pressure will be applied to the VE
LT
RON DPT 2500-
plus
, unit will be
programmed to recognize these pressures as zero and span for transmitter input calibration.
1. While in Main Menu, scroll to:
Transmitter Input
Calibration
2. Press , and display will indicate:
Input Zero Calib.
3. Press , and display will indicate:
Input Zero Calib.
-- Push ENTER --
4. Slide switch S1 - "AZ V
a
lve" to the ON position.
5. Press , and display will indicate:
Transducer Zero
Settle Time:4
Display will count down to 0, after which it will indicate: Input Zero Done
-- Push ESCAPE --
Display will count down to 0, after which it will indicate: Input Span Done
-- Push ESCAPE --
Note: If pressure input is less than 40% or greater than 1
1
0% of transducer's Natural s
pa
n value (see
Factory Set-Up Information Sheet), display will indicate:
Bad Input S
p
an
-- Push ESCAPE --
If this occurs, check input pressure (as read on manometer), and readjust as necessary
.
Press and
repeat S
t
eps 7 through 10.
11. Remove input pressure from High port on VELTRON DPT 2500-
plus
.
12. Press and then , display will indicate: Return to
MAIN MENU
13. Press , and display will return to Main Menu.
6. Press and then , display will indicate:
Input S
p
an Calib.
7. Press , and display will indicate:
Input Span Calib.
-- Push ENTER --
8. Slide switch S1 - "AZ Valve" to the OFF position.
9. Apply input pressure (as read on manometer) to the High port of the VE
LT
RON DPT 2500-
plus
. Adjust
pressure to equal the transducer natural s
pa
n value (see Factory Set-Up Information Sheet for this value).
10. Press , and display will indicate:
Transducer Span
Settle Time:4