5.9 – AUTO-zero CONFIGURATION
User can turn AUTO-zero function ON or OFF, and select activation interval.
1. While in Main Menu, use or to scroll to:
Auto-Zero
Configuration
2. Press to enter
A
UTO-zero Configuration menu. Display will indicate: Auto-Zero Off/On
Selection
3. Press and display will indicate current setting of
A
UTO-zero (OFF or ON).
4. Use or to change setting. Once desired setting is displayed, press , new setting will be stored in
memory and display will return to
A
UTO-zero Configuration menu as in S
t
ep 2.
Note: If user desires not to change the setting and return to
A
UTO-zero Configuration menu press . Unit
will remain programmed as it was originally.
5. Use or to select remaining p
a
rameters to be changed.
6. Follow Step 4 to make any changes to p
a
rameters.
7. To return to Main Menu select Return to MAIN MENU in
A
UTO-zero Configuration menu and press .
SECTION 5 – OPERATION
19
X
Auto-Zero Off/On
ON
Default selection shown.
Available selections:
ON or OFF
- Auto-Zero Off/On Selection
- Auto-Zero Interval Selection
- Return to MAIN MENU
Auto-Zero Interval
1 Hour
1 to 24 hours
in 1 hr. increments
User Setup Main Menu
Auto-Zero Configuration
Return to
MAIN MENU
- Low Pass Filter Selection
Auto-Zero Configuration
- Transducer Span Selection
Available selections: