5.10 – TRANSDUCER SPAN SELECTION
Displays the natural span (maximum full scale s
pa
n) of the transducer inst
a
lled in the VELTRON DPT 2500-
plus
. The
displayed natural span is for user/technician reference only and should not be changed unless a new transducer of
differential natural span has been inst
a
lled. Also displays the operating span.
SECTION 5 – OPERATION
20
1. While in Main Menu, use or to scroll to:
Transducer Span
Selection
2. Press to enter Transducer Span Selection menu. Display will indicate: Xdcr Natural S
p
an
Selection
3. Press and display indicates the natural sp
a
n of the installed transducer (0.05, 0.10, 0.25, 0.50, 0.75, 1.00,
1.50, 2.00, 2.50, 3.00, 5.00, 10.00, 15.00, 25.00, 50.00, 100.00, 150.00, 200.00, or 250 in. WC).
4. Use or to change setting. Once desired setting is displayed press . New setting will be stored in
memory and display will return to Main Menu.
Caution: Only change setting if a transducer of different natural span has been inst
a
lled.
Note: If user desires not to change the setting and return to Main Menu, press . Unit will remain
programmed as it was originally.
5. Use or to select remaining p
a
rameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Transducer Span Selection Menu and press .
Note: If unit is configured as bi-polar, Xdcr Natural Span selections will be in the form of ±x.xx, and Xdcr
Operating Span will have a Min and Max selection.
X
- Auto-Zero Configuration
Transducer Span Selection
- Transmitter Input Calib.
- Xdcr Natural Span Selection
- Xdcr Operating Span Selection
- Return to MAIN MENU
Transducer Span Selection
Xdcr Natural Span
0.25 in. WC
Xdcr Operating Span
0.2500 in. WC
Return to
MAIN MENU
Adjustable from 40% to
100% of selected Natural
Span.
Default selection shown.
Available selections
:
User Setup Main Menu
0.05, 0.10, 0.25, 0.50,
0.75, 1.00, 1.50, 2.00,
2.50, 3.00, 5.00, 10.00,
15.00, 25.00, 50.00,
100.00, 150.00, 200.00,
or 250.00