5.6 – CONFIGURATION PROGRAMMING
With power ON and initialization complete (see Section 5.2), press and display will indicate:
USER SETUP
Pressing will enter the user into the Main Menu of configuration programming. The display will indicate:
Transmitter Scaling
and Configuration
By using and , the user can scroll through the following selections:
SECTION 5 – OPERATION
MAIN MENU SELECTION
Transmitter Scaling &
Configuration
Low Pass Filter Selection
AUTO-zero Configuration
Transducer S
p
an Selection
Transmitter Input Calibration
Transmitter Output Calibration
Exit User Setup
DESCRIPTION
Allows for the configuration of process variable such as: Square root ON/OFF,
process t
y
pe, process minimum/ maximum/unit
s
, and percent lockdown.
Selects amount of filtering applied to transducer output and to the display.
Turns AUTO-zero function ON or OFF, and select
s
activation interval.
Allows for displaying the natural span of
th
e installed transducer, and selecting
the operating s
pa
n.
Allows for the zeroing and sp
a
nning transmitter analog Input
s
.
Allows for the zeroing and spanning of transmitter analog Output
s
.
Returns display to
Normal
operation.