5.7 – TRANSMITTER SCALING & CONFIGURATION (con't)
1. While in Main Menu, use or to scroll to:
Transmitter Scaling
and Configuration
2. Press to enter Transmitter Scaling & Configuration menu. Display will indicate: Square Root On/Off
Configuration
3. Press and display will indicate current setting of Square Root (OFF or ON).
4. Use or to change setting. Once desired setting is displayed, press , new setting will be stored in
memory and display will return to Transmitter Scaling & Configuration menu as in S
t
ep 2.
Note: If user desires not to change the setting and return to the Transmitter Scaling & Configuration sub-menu,
press . Unit will remain programmed as it was originally.
5. Use or to select remaining p
a
rameters to be changed within the Process Configuration sub-menu.
See the following Unit
s
Lists for the available Process Unit
s
selections for the appropriate Process T
y
pe.
See the following Format List for the available Process Format selections.
6. Follow S
t
ep 4 to make any changes to parameters.
7. To return to the Main Menu, select Return to Main Menu in the T
r
ansmitter Scaling & Configuration menu and
press .
Note: If Process Minimum is selected to be a value greater than zero (0), Output will not increase until the actual
process exceeds this selected value. This is known as "Zero Suppression".
Zero Suppression (Process Minimum) can be set up to 60% of the Process Maximum selected.
Display of process is not af
f
ected by this selection, and will indicate the actual process value.