VELTRON DPT 2500-
plus
Air Monitor Corporation
116-047-20.PMD (5/5/11)
VELTRON DPT 2500-
plus
- IO&M Manual
SECTION 6 – CALIBRATION
6.4 – TRANSMITTER OUTPUT CALIBRATION (con't)
6. Once an acceptable zero reading is obt
a
ined press and then and display will indicate:
Output Span Calib.
7. Press , and display will indicate:
Output Span Calib.
Perform Calibration
8. With DMM still connected as in S
t
ep 4, reading should be at maximum value of 20.00 ± 0.01mA, 5.00 ±
0.01VDC, or 10.00 ± 0.01VDC.
9. If DMM is reading out of tolerance, use or to adjust VELTRON DPT 2500-
plus
output for an accept
a
ble
DMM reading.
10. Once an acceptable sp
a
n reading is obtained, press and then and display will indicate.
Return to
MAIN MENU
11. Press and scroll Main Menu to:
EXIT
User Setup
12. Press and VELTRON DPT 2500-
plus
will return to
Normal
mode of operation.
27