SECTION 6 – CALIBRATION
6.3 – TRANSMITTER INPUT CALIBRATION (con't)
6.3.2
For Units With Bi-Polar Spans.
Minimum and maximum transducer natural sp
a
n pressure will be applied to the VELTRON DPT 2500-
plus
, unit
will be programmed to recognize these pressures as zero and sp
a
n for transmitter input calibration.
1. Connect input pressure to Low
P
ort of VE
LT
RON DPT 2500-
plus
.
Transmitter Input
2. While in Main Menu, scroll to:
Calibration
3. Press , and display will indicate:
Input Zero Calib.
4. Press , and display will indicate:
Input Zero Calib.
-- Push ENTER --
5. Slide switch S1 - "AZ V
al
ve" to the OFF position.
6. Apply input pressure (as read on manometer) to the Low Port of the VE
LT
RON DPT 2500-
plus
.
Adjust pressure to equal the positive equivalent of the minimum (negative) transducer natural sp
an
value (see Factory Set-Up Information Sheet for this value).
7. Press , and display will indicate:
Transducer Zero
Settle Time:4
Display will count down to 0, after which it will indicate: Input Zero Done
-- Push ESCAPE --
24
8. Press and then , display will indicate:
Input S
p
an Calib.
9. Press , and display will indicate:
Input S
p
an Calib.
-- PUSH ENTER --
10. Connect input pressure to the High Port of the VELTRON DPT 2500-
plus
.
11.Apply input pressure (as read on manometer) to the High Port of the VE
LT
RON DPT 2500-
plus
.
Adjust pressure to equal the maximum (positive) transducer natural sp
a
n value (see Factory Set-Up
Information Sheet for this value).
12. Press , and display will indicate:
Transducer Span
Settle Time:4
Display will count down to 0, after which it will indicate: Input S
p
an Done
-- Push ESCAPE --
Note: If pressure input is less than 40% or greater than 1
1
0% of transducer's maximum (positive)
Natural span value range (see Factory Set-Up Information Sheet), display will indicate:
Bad Input S
p
an
-- Push ESCAPE --
If this occurs, check input pressure (as read on manometer), and readjust as necessary
.
Press and
repeat S
t
eps 9 through 12.