SECTION 6 – CALIBRATION
58
6.4 – TRANSMITTER OUTPUT CALIBRATION (con't)
6. Once an acceptable zero reading is obtained, press
ENT
and then
UP
and display will indicate:
Output 1 Span
7. Press
ENT
, and display will indicate:
Transmitter Span
Perform Calibration
8. With DMM still connected as in Step 4, reading should be at maximum value; 10.00 ± 0.01 volts, 5.00 ± 0.01 volts,
or 20.00 ± 0.01mA.
9. If DMM is reading out of tolerance, use
UP
or
DN
to adjust MASS-tron II/CEM output for an acceptable DMM
reading.
10. Once an acceptable span reading is obtained, press
ENT
and then
UP
and display will indicate.
Output 2 Zero
11.Repeat Steps 3 through 10 for other Outputs. For Temperature Output 2, connect DMM across terminals 2 and 3;
for Absolute Pressure Output 3 across terminals 4 and 6, and for Analog Output 4 across terminals 5 and 6 (see
Figure 4.5).
12. Press
UP
until display indicates:
Return to
MAIN MENU
13. Press
ENT
and scroll Main Menu to:
EXIT
Operator Setup
14. Press
ENT
and MASS-tron II/CEM will return to
Normal
mode of operation.