SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION (con't)
26
Temperature
Off/On Selection
2
Default selection shown.
Available selections:
ON or OFF
Temperature On/Off
ON
Input Linearization
Selection
Input Linearization
OFF
Thermocouple TypeE
Thermocouple Type J
Thermocouple TypeK
Themocouple Type T
100
Platinum RTD
Temperature
Type Selection
6
Temperature Type
Thermocouple TypeK
EXIT
Temperature Configuration
2
Available only if Density Compensation is OFF.
ON or OFF
Minimum Temp.
Selection
Minimum Temp.
0°F
Default Temp.
Selection
7
Default Temp.
250°F
Default Temperature
Drive Output High
8
Drive Output Low
9
Temp. Fault Output
Selection
Temp. Fault Output
DEFAULTTEMPERATURE
-50 to +50°F
-50 to +10°C
410 to 510°R
223 to 283°K
Maximum Temp.
Selection
Maximum Temp.
500°F
Min. plus 50 to 2000°F
Min. plus 30 to 1090°C
Min. plus 50 to 2460°R
Min. plus 30 to 1300°K
-50 to 2000°F
-50 to 1090°C
410 to 2460°R
223 to 1300°K
6
Available only if Input Linearization is ON.
7 Default Temperature is used when a faulty
temperature signal is received.
Exits to Trans.
Scaling &
Configuration Menu
8 Output will increase to 10% above max.
9 Output will decrease to 10% below min.
9. While in Transmitter Scaling & Configuration menu, use
UP
or
DOWN
to scroll to:
Temperature
Configuration
10. Press
ENT
to enter the Temperature Configuration sub-menu.
If Density Compensation is ON (see Process Configuration above), display will indicate: Input Linearization
Selection
If Density Compensation is OFF display will indicate:
Temperature Off/On
Selection
11. Press
ENT
and display will indicate current selection of applicable menu from Step 10.