SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION (con't)
1. While in Main Menu, use
UP
or
DN
to scroll to:
Transmitter Scaling
and Configuration
2. Press
ENT
to enter Transmitter Scaling & Configuration menu. Display will indicate:
Process
Configuration
3. Press
ENT
to enter the Process Configuration sub-menu. Display will indicate: Density Comp. Off/On
Selection
4. Press
ENT
and display will indicate current setting of Density Compensation (OFF or ON).
5. Use
UP
or
DN
to change setting. Once desired setting is displayed, press
ENT
, new setting will be stored in
memory and display will return to Process Configuration sub-menu as in Step 3.
Note: If user desires not to change the setting and return to the Process Configuration sub-menu, press
ESC
.
Unit will remain programmed as it was originally.
6. Use
UP
or
DN
to select remaining parameters to be changed within the Process Configuration sub-menu.
See the follow Units Lists for the available Process Units selections for the appropriate Process Type.
See the following Format List for the available Process Format selections.
7. Follow Step 5 to make any changes to parameters.
8. To return to the Transmitter Scaling & Configuration menu, select EXIT in the Process Configuration sub-menu
and press
ENT
.
Note:
If Process Minimum is selected to be a value greater than zero (0), Transmitter Output 1 will not increase
until the actual process exceeds this selected value. This is known as "Zero Suppression".
Zero Suppression (Process Minimum) can be set up to 60% of the Process Maximum selected.
Display of process is not affected by this selection, and will indicate the actual process value.
If Analog Output 2, 3 and/or 4 is selected to represent TRANSMITTER, it will act the same as Transmitter
Output 1.