MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION
This Main Menu selection is where all application specific data is entered to configure the MASS-tron II/CEM for a
unique application. Data is entered in sub-menu, Process Configuration, and as applicable, sub-menus, Temperature
Configuration and Absolute Pressure Configuration. Typical data includes: Process Type, Process Minimum/Maximum,
Density Compensation ON/OFF, Temperature Range, Absolute Pressure Range, Duct Area/Units, etc.
Note:
Factory has entered data in this section based on customer supplied information. Data can be reviewed and
verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information Sheet.
Review this information
BEFORE
making any changes, as they can have a significant effect on the operation of
the MASS-tron II/CEM.
Under a fourth sub-menu, Calculator for Max Diff. Pres. or Flow, user can calculate either maximum flow or maximum
differential pressure (D.P.) when operating parameters have changed.
Each sub-menu will be addressed separately.
20