MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
4.5 – POWER/SIGNAL CONNECTIONS (con't)
Transmitter/AUTO-cal Reporting Output 1 (Terminals 1 and 3).
This output is sourced (powered) by the MASS-tron
II/CEM.
4-20mADC: Maximum load resistance is 750 ohms.
0-10VDC:
Minimum load resistance is 5000 ohms.
0-5VDC:
Minimum load resistance is 2500 ohms.
Temperature Output 2 (Terminals 2 and 3).
This output is sourced (powered) by the MASS-tron II/CEM.
4-20mADC: Maximum load resistance is 750 ohms.
0-10VDC:
Minimum load resistance is 5000 ohms.
0-5VDC:
Minimum load resistance is 2500 ohms.
Absolute Pressure Output 3 (Terminals 4 and 6).
This output is sourced (powered) by the MASS-tron II/CEM.
4-20mADC: Maximum load resistance is 750 ohms.
0-10VDC:
Minimum load resistance is 5000 ohms.
0-5VDC:
Minimum load resistance is 2500 ohms.
Analog Output 4 (Terminals 5 and 6).
This output is sourced (powered) by the MASS-tron II/CEM.
4-20mADC: Maximum load resistance is 750 ohms.
0-10VDC:
Minimum load resistance is 5000 ohms.
0-5VDC:
Minimum load resistance is 2500 ohms.
Temperature Input (Terminals 7, 8, and 10)
. Follow the appropriate figure below for connecting a temperature input
signal.
Figure 4.4
Figure 4.5
AUTO-purge "Start" Signal (Terminals 11 and 13).
Customer to provide momentary (0.5 to 10 second unpowered)
dry contact as notification of AUTO-purge cycle initiation (typically from "smart" relay). Upon receiving this signal,
transmitter hold will be activated.
External AUTO-cal Start (Terminals 12 and 13).
Customer to provide momentary (0.5 to 10 second unpowered) dry
contact to initiate AUTO-cal cycle.
Input Power (Terminals 14, 15, and 16).
Power required by MASS-tron II/CEM must be connected to Terminals 15
and 16. Earth ground should be connected to Terminal 14. When powering multiple units from one power source, polarity
must be maintained.
Low Flow Alarm (Terminals 21, 22, and 23).
Customer to connect according to desired alarm logic. Figure 4.3
indicates de-energized (alarm off) state.
Review Factory Set-Up Information Sheet
for your signal type.
Review Factory Set-Up Information Sheet
for your signal type.
Review Factory Set-Up Information Sheet
for your signal type.
Review Factory Set-Up Information Sheet
for your signal type.
SECTION 4 – INSTALLATION
9