MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
SECTION 5 – OPERATION
33
Auto-Zero Off / On
ON
Default selection shown.
Available selections:
ON or OFF
- Auto-Zero Off / On Selection
- Auto-Zero Interval Selection
- Return to MAIN MENU
Auto-Zero Interval
2 Hour
1 to 24 hours
in 1 hr. increments
Auto-Zero Configuration
Return to
MAIN MENU
- Low Pass Filter Selection
Auto-Zero Configuration
- Auto-Purge Configuration
Operator Setup Main Menu
5.10 – AUTO-zero CONFIGURATION
User can turn AUTO-zero function ON or OFF, and select activation interval.
1. While in Main Menu, use
UP
or
DN
to scroll to:
Auto-Zero
Configuration
2. Press
ENT
to enter AUTO-zero Configuration menu. Display will indicate: Auto-Zero Off/On
Selection
3. Press
ENT
and display will indicate current setting of AUTO-zero (OFF or ON).
4. Use
UP
or
DN
to change setting. Once desired setting is displayed, press
ENT
and new setting will be stored in
memory and display will return to AUTO-zero Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to AUTO-zero Configuration menu, press
ESC
. Unit
will remain programmed as it was originally.
5. Use
UP
or
DN
to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in AUTO-zero Configuration menu and press
ENT
.