MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
SECTION 5 – OPERATION
47
5.21 – TRANSMITTER OUTPUT CALIBRATION
See Section 6.4 – Calibration for details on Transmitter Output Calibration.
5.20 – TRANSMITTER INPUT CALIBRATION
See Section 6.3 – Calibration for details on Transmitter Input Calibration.
- Transducer Span Selection
Transmitter Input Calib.
- Transmitter Output Calib.
Transmitter Input Calib.
See Calibration
Instructions
- Transducer Zero
- Transducer Span
- Abs. Pressure Zero
- Abs. Pressure Span
- Temperature Zero
- Temperature Span
- Return to Main Menu
Operator Setup Main Menu
- Output 1 Zero
- Output 1 Span
- Output 2 Zero
- Output 2 Span
- Output 3 Zero
- Output 3 Span
- Output 4 Zero
- Output 4 Span
- Return to MAIN MENU
See Calibration
Instructions
Transmitter Output Calib.
Operator Setup Main Menu
- Transmitter Input Calib.
Transmitter Output Calib.
- Power Supply Calibration
5.22 – POWER SUPPLY CALIBRATION
User can adjust power supply Voltage to an optimum value. The voltage has been adjusted at the Factory and should
not require adjustment.
1. While in Main Menu, use
UP
or
DN
to scroll to:
Power Supply
Calibration
2. Press
ENT
and display will indicate current power supply voltage on line 2. Set To 7.000 ± 0.100
7.000 VDC
3. If supply voltage is less than 6.900V or greater than 7.100V, adjust R36 on I/O Board (see Figure 5.2) until
acceptable voltage reading is displayed on line 2.
4. When done, press
ENT
to return to Main Menu.
Set to 7.000 +-0.100
7.000 VDC
See Calibration
Instructions
- Transmitter Output Calib.
Power Supply Calibration
- Xdcr Characterizat'n Select
Operator Setup Main Menu