![AIC COILMASTER 100 Скачать руководство пользователя страница 83](http://html1.mh-extra.com/html/aic/coilmaster-100/coilmaster-100_installation-and-maintenance-manual-for-the-installer-and-the-user_2870753083.webp)
I-83
G-084383_EN • 03
A
dditionAl
i
nformAtion
for
the
i
nstAller
Error
code
Fault description
Explanation
Action(s)
329
Extension module/mixing
group same function
Check confi guration in parameters list.
330
Sensor input BX1 without
function
Connect temperature sensor in BX
terminal
331
Sensor input BX2 without
function
Connect temperature sensor in BX
terminal
332
Sensor input BX3 without
function
Connect temperature sensor in BX
terminal
333
Sensor input BX4 without
function
Connect temperature sensor in BX
terminal
335
Sensor input BX21 without
function
Connect temperature sensor in BX
terminal
336
Sensor input BX22 without
function
Connect temperature sensor in BX
terminal
341
Sensor B6 missing
Solar sensor missing
Check parameters, connection and
component.
349
Buff er storage tank return
valve Y15 missing
Check connection of return valve Y15.
Replace as required.
350
Buff er storage tank ad-
dress error
Correct device address.
351
Primary controller/ system
pump, address error
Correct device address.
352
Pressureless header, ad-
dress error
Correct device address.
353
Sensor B10 missing
Common fl ow sensor missing
Check parameters, connection and
component
371
Flow temperature heating
circuit 3
Check the circuit for fault insulation and
heat losses.
372
Temperature limiter heating
circuit 3
Allow the circuit to cool down and carry
out reset; if the fault occurs several
times inform AIC technical suport.
378
Internal repetition
Contact AIC technical support
382
Repetition speed
Contact AIC technical support
384
Extraneous light
Shut off gas supply and contact AIC
technical support
385
Mains undervoltage
Check electric supply in boiler terminals
386
Fan speed tolerance
Check air supply
388
DHW sensor no function
Check connection and sensor. Replace
as required.
391
Room controller 1
Check addresses and parameters
392
Room controller 2
393
Room controller 3
426
Feedback fl ue gas damper
Check the connection and component
427
Confi guration fl ue gas
damper
Check confi guration parameters
Содержание COILMASTER 100
Страница 67: ...X3 3 4 5 2 Fig 21 CM 60 70 80 Removing and Installing the Burner 1 6 I 67 G 084383_EN 03 Maintenance...
Страница 69: ...3 5 2 1 Fig 22 CM 100 120 Removing and Installing the Burner I 69 G 084383_EN 03 Maintenance...
Страница 92: ...I 92 G 084383_EN 03 Declaration of Conformity...
Страница 93: ...I 93 G 084383_EN 03 NOTES...
Страница 94: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...