![AIC COILMASTER 100 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/aic/coilmaster-100/coilmaster-100_installation-and-maintenance-manual-for-the-installer-and-the-user_2870753059.webp)
I-59
G-084383_EN • 03
M
aintenance
Tasks
@ inspection
(1 year)
@ maintenance
(2 years max)
Check that the boiler room ventilation / boiler air and flue ducts are
unobstructed.
X
X
Verify flue gas and combustion air ducts are in good condition,
sealed tight and properly supported.
X
X
Open the front panel and check the general condition inside the
cabinet. Clean and vacuum as required.
X
X
Check the correct operation of the flue pressure switch, refer to
“Checking the Flue Pressure Switch operation” on page I-62
X
X
Clean the condensate trap. Remove condensate trap and flush with
clear water, see
“Cleaning the Condensate Pipe and Trap” on
page
I-61
X
X
Clean/service the condensate neutralisation system (if any). Refer
to manufacturer’s documentation.
X
X
Clean any filter/dirt separator, plate heat exchanger or balance
header present in the hydraulic system, as required. Refer to man-
ufacturer’s documentation.
X
X
Check for leaks, both inside and outside the appliance: water, gas,
flue and condensate.
X
X
Check boiler water pressure (at least
1.2 bar when cold). Top up
the system with water if required.
X
X
Check the operation of the burner (flame) through the sight glass
and that the combustion parameters (CO & CO
2
) are according to
requirements. See
“Combustion and Gas Data” on page G-18
.
X
X
Check the gas pressure and that the gas supply shut-off devices
are operating properly.
X
Check that the pump(s) is/are operating properly.
X
Check that the fan is operating properly.
X
Remove the burner and check its general condition. Clean as
required. See
“Removing and Installing the Burner -
CM 60 - 70 - 80” on page I-66
or
“Removing and Installing
the Burner - CM 100 - 120” on page I-68
.
X
Replace the ignition and ionisation electrodes. Refer to
“Removing and
Installing the Ignition and Ionisation Electrodes” on page I-63
.
X
Check all control wiring and connections.
X
X
Check the condition of the combustion chamber and clean it if
required. See
“Checking and Cleaning the Combustion Cham
-
ber” on page I-70.
X
Check water quality and record in log sheet, See
“Water Param-
eters - Log Sheet” on page
I-91
X
X
Record the operations and results in the Log Sheets provided at
the end of the manual
X
X
Maintenance Requirements
Содержание COILMASTER 100
Страница 67: ...X3 3 4 5 2 Fig 21 CM 60 70 80 Removing and Installing the Burner 1 6 I 67 G 084383_EN 03 Maintenance...
Страница 69: ...3 5 2 1 Fig 22 CM 100 120 Removing and Installing the Burner I 69 G 084383_EN 03 Maintenance...
Страница 92: ...I 92 G 084383_EN 03 Declaration of Conformity...
Страница 93: ...I 93 G 084383_EN 03 NOTES...
Страница 94: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...