G-084383_EN • 03
P
roduct
I
nstallatIon
600mm maximum
300mm minimum
temperature relief valve to tundish
Metal discharge pipe (D2) tundish with
continuous fall. See 3.56, Table G3 and
worked example
Tundish
Discharge below fixed
grating (3.61 gives
alternative points of
discharge)
Fixed grating
Trapped gulley
Valve outlet size
Minimum size of dis-
charge pipe D1
Minimum size of dis-
charge pipe D2 from
tundish
Maximum resistance
allowed, expressed
as a length of straight
pipe (i.e. no elbows or
bends)
Resistance created by
each elbow or bend.
G½
15mm
22mm
28mm
35mm
Up to 9m
Up to 8m
Up to 27m
0.8m
1.0m
1.4m
G¾
22mm
28mm
35mm
42mm
Up to 9m
Up to 8m
Up to 27m
1.0m
1.4m
1.7m
G1
28mm
35mm
42mm
54mm
Up to 9m
Up to 8m
Up to 27m
1.4m
1.7m
2.3m
Figure G3: Typical discharge pipe arrangement
Table G3 – Sizing of copper discharge pipe ‘D2’ for common temperature relief valve outlet sizes
Содержание COILMASTER 100
Страница 67: ...X3 3 4 5 2 Fig 21 CM 60 70 80 Removing and Installing the Burner 1 6 I 67 G 084383_EN 03 Maintenance...
Страница 69: ...3 5 2 1 Fig 22 CM 100 120 Removing and Installing the Burner I 69 G 084383_EN 03 Maintenance...
Страница 92: ...I 92 G 084383_EN 03 Declaration of Conformity...
Страница 93: ...I 93 G 084383_EN 03 NOTES...
Страница 94: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...