I-82
G-084383_EN • 03
A
dditionAl
i
nformAtion
for
the
i
nstAller
Error
code
Fault description
Explanation
Action(s)
183
Unit in parametrization
mode
Wait until parametrization process is
complete
193
Start prevention signal
input
Short circuit or Open circuit fl ue
pressure switch.
Check connection and sensor. Replace
as required.
195
Maximum duration of the
refi ll per charging exceeded
Check automatic refi ll system.
The use of an automatic refi ll system is not recommended
196
Maximum duration of the
refi ll per week exceeded
Check automatic refi ll system.
The use of an automatic refi ll system is not recommended
209
Fault heating circuit
Check the heating circuit confi guration.
Reset to default parameters
216
Fault boiler
Check the heating circuit confi guration.
Reset to default parameters
217
Sensor error
Check connection and sensor. Replace
as required.
218
Pressure supervision
Check system pressure.
243
Swimming pool sensor,
error
Check connection and sensor. Replace
as required.
260
Flow temperature 3, sensor
error
Check connection and sensor. Replace
as required.
270
Temperature diff erence,
heat exchanger too large
Check the heating system external hy-
draulic components.
317
Mains frequency outside
permissible range
Check correct electric supply in boiler
terminals.
320
DHW charging tempera-
ture, sensor error
Check connection and sensor. Replace
as required.
321
DHW outlet temperature,
sensor error
Check connection and sensor. Replace
as required.
322
Water pressure 3 too high
Release the water to a suitable pressure.
323
Water pressure 3 too low
Top up the system with water to reach a
suitable pressure.
324
Input BX, same sensors
Check confi guration in parameters list
325
Input BX/extension mod-
ule, same sensors
Check confi guration in parameters list.
326
Input BX/mixing group,
same sensors
Check confi guration in parameters list.
327
Extension module, same
function
Check confi guration in parameters list.
328
Mixing group, same func-
tion
Check confi guration in parameters list.
i
i
Содержание COILMASTER 100
Страница 67: ...X3 3 4 5 2 Fig 21 CM 60 70 80 Removing and Installing the Burner 1 6 I 67 G 084383_EN 03 Maintenance...
Страница 69: ...3 5 2 1 Fig 22 CM 100 120 Removing and Installing the Burner I 69 G 084383_EN 03 Maintenance...
Страница 92: ...I 92 G 084383_EN 03 Declaration of Conformity...
Страница 93: ...I 93 G 084383_EN 03 NOTES...
Страница 94: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...