Error
code
Fault description
Explanation
Action(s)
130
Flue gas temperature limit
exceeded
Heat engine is overheating
Check causes of high temps
Check connection and sensor. Replace
as required
Check connection and chimney.
132
Gas pressure switch safety
shut down
Lack of gas
Check gas supply and pressure
Check connection and component
133
Safety time for establish-
ment of fl ame exceeded
Lack of gas,
Polarity of mains connection,
safety period,
Reset, if the fault re-occurs more than 3
times, contact AIC technical support.
Check ignition electrode and ionization
current
146
Confi guration error sensor/
controlling elements
Check sensor confi guration or replace
component
151
LMS14… error, internally
Check parameters (see adjustment table
installer and/or call-up values)
Reset controller and/or replace as
required,
Contact AIC technical support.
152
Parameterization error
Incorrect / Confl icting parame-
ters input.
Verify parameters or reset to default
parameters
153
Unit manually locked
Reset button stuck in
Check reset button
160
Fan speed threshold not
reached
Fan possibly defective, speed
threshold set wrongly.
Check parameters, connections and
component. Replace as required
162
Air pressure switch error
Air pressure switch does not
close
Check connection and adjustments on
air pressure switch. Replace as required.
164
Flow/pressure switch,
heating circuit error
Check connection and switches in HC.
Replase as required
166
Air pressure switch error
Air pressure switch does not
open
Check connection and adjustments on
air pressure switch. Replace as required.
170
Error water pressure sen-
sor, primary side
Check connection and sensor. Replace
as required.
171
Alarm contact 1 active
Correct the active fault
172
Alarm contact 2 active
173
Alarm contact 3 active
174
Alarm contact 4 active
176
Water pressure 2 too high
Release the water to a suitable pressure.
177
Water pressure 2 too low
Top up the system with water to reach a
suitable pressure.
178
Temperature limiter heating
circuit 1
Allow the circuit to cool down and carry
out reset; if the fault occurs several
times inform AIC technical suport.
179
Temperature limiter heating
circuit 2
Allow the circuit to cool down and carry
out reset; if the fault occurs several
times inform AIC technical suport.
Содержание COILMASTER 100
Страница 67: ...X3 3 4 5 2 Fig 21 CM 60 70 80 Removing and Installing the Burner 1 6 I 67 G 084383_EN 03 Maintenance...
Страница 69: ...3 5 2 1 Fig 22 CM 100 120 Removing and Installing the Burner I 69 G 084383_EN 03 Maintenance...
Страница 92: ...I 92 G 084383_EN 03 Declaration of Conformity...
Страница 93: ...I 93 G 084383_EN 03 NOTES...
Страница 94: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...