Measurement Category
The U1602A and U1604A oscilloscope is intended to be used for
measurement in Measurement Category III, 300 V for scope measurement
and Measurement Category III, 300 V and Category II, 600 V for
multimeter measurement.
Measurement Category Definitions
Measurement CAT I is for measurements performed on circuits not
directly connected to MAINS. Examples are measurements on circuits not
derived from MAINS, and specially protected (internal) mains- derived
circuits.
Measurement CAT II are measurements performed on circuits directly
connected to the low voltage installation. Examples are measurements on
household appliances, portable tools and similar equipment.
Measurement CAT III are measurements performed in the building
installation. Examples are measurements on distribution boards,
circuit- breakers, wiring, including cables, bus- bars, junction boxes,
switches, socket- outlets in the fixed installation, and equipment for
industrial use and some other equipment including stationary motors with
permanent connection to the fixed installation.
Measurement CAT IV are measurements performed at the source of the
low- voltage installation. Examples are electricity meters and measurements
on primary over current protection devices and ripple control units.