– 14 –
ECP Configuration (Question 8)
Question 8.
Device Addr
Skip this question if using zones (if you answered “N” to
Question 1) and go to Question 9.
If using ECP mode (you answered “Y” to Question 1), enter the ECP
device address of the radio. For VIA 30+, VISTA-10SE, and
VISTA-20SE this must be address 3. For other control panels, see
the control panel’s Installation Instructions. Skip to question 31.
Pulse/Delay Zone Selection (Questions 9-14)
By configuring a zone as a pulsed zone, it is possible to use the output of a panel bell/siren driver to
activate the radio directly when the signal from this driver is a pulsed output for fire and a continuous
output for burglary. To implement a fire/burglary. detection at the radio, connect the driver output directly
to 2 zones on the 7835C. Program the fire zone as a pulsed zone and the burglary zone as a delayed zone
(this is to prevent this zone from reporting an alarm when the pulsed signals are detected). The number of
pulses and the length of delay will depend on the particular panel or siren driver being used, and is
therefore a programmable feature.
Zones designated as open/close or telco zones cannot be programmed for pulse. If this occurs, the
pulse detection on the zone is automatically disabled.
UL
Questions 9-14: Select “N” for Pulse and “00” for Delay for UL installations.
Question 9
Pulse Z1 (Y/N)
Press “Y” if zone 1 is connected to a pulsed bell output. Question 9b will appear. If
you pressed “N”, the following appears.
Question 9a
Z1 Delay
(00-127)
Enter the reporting delay from 1-127 seconds for zone 1.
Enter “00” for no reporting delay.
Question 9b
Pulse Cnt?
(03 – 254)
If you answered “Y” to “Pulse Z1,” the next question will be
“Pulse Cnt?” Input the number of pulses required to place the
zone in alarm.
Question 10
Pulse Z2 (Y/N)
Press “Y” if zone 2 is connected to a pulsed bell output. Question 10b will appear.
If you press “N,” the following appears.
Question 10a
Z2 Delay
(00-127)
Enter the reporting delay from 1-127 seconds for zone 2.
Enter “00” for no reporting delay.
Question 10b
Pulse Cnt?
(03 - 254)
If you answered “Y” to “Pulse Z2,” the next question will be
“Pulse Cnt?” Input the number of pulses required to place the
zone in alarm.
Question 11
Pulse Z3 (Y/N)
Press “Y” if zone 3 is connected to a pulsed bell output. Question 11b will appear.
If you press “N,” the following appears.
Question 11a
Z3 Delay
(00-127)
Enter the reporting delay from 1-127 seconds for zone 3.
Enter “00” for no reporting delay.
Question 11b
Pulse Cnt?
(03 - 254)
If you answered “Y” to “Pulse Z3,” the next question will be
“Pulse Cnt?” Input the number of pulses required to place the
zone in alarm.