– 18 –
Question 32
AC Loss RPT
(Y/N)
If you answered “yes” (Y) to “AC Loss RPT,” the radio will report
the loss of AC line voltage within a 10-to 40-minute window after its
detection. If this feature is disabled (by pressing “N”), AC loss
alarms will be suppressed. NOTE: In either case, if a battery is
installed, low-battery messages will be sent as detected. Must be
“Y” for UL installations.
Question 33
Bat Present
(Y/N)
Press “Y” if optional battery will be used. Must be “Y” for UL
installations (a battery must be installed).
If ECP mode is enabled, skip to question 35.
Question 34
FLT REL ON
(Y/N)
Press “Y” if fail-safe mode is desired. In this mode, the fault relay is
normally energized and will de-energize in the event of a radio fault.
Note that fail-safe mode draws slightly more standby current. Must
be “Y” for UL installations.
Question 35
Flt Time (min)
Enter in minutes 1 - 99 the time delay before the fault relay will
change state, after a loss of contact with the network.
If ECP mode is enabled, skip to question 45.
Redundant Central Station Reporting (Questions 36-47)
Question 36
2nd CS (Y/N)
Press “Y” if redundant reporting to a second central station is
desired. Press “N” if not desired (skip to end).
Question 37
2CS Z1 (Y/N)
Press “Y” to enable reporting to second central station for zone 1.
Enter “N” to disable reporting.
Question 38
2CS Z2 (Y/N)
Press “Y” to enable reporting to second central station for zone 2.
Enter “N” to disable reporting.
Question 39
2CS Z3 (Y/N)
Press “Y” to enable reporting to second central station for zone 3.
Enter “N” to disable reporting.
Question 40
2CS Z4 (Y/N)
Press “Y” to enable reporting to second central station for zone 4.
Enter “N” to disable reporting.
Question 41
2CS Z5 (Y/N)
Press “Y” to enable reporting to second central station for zone 5.
Enter “N” to disable reporting.
Question 42
2CS Z6 (Y/N)
Press “Y” to enable reporting to second central station for zone 6.
Enter “N” to disable reporting.
Question 43
2CS Tamp (Y/N)
Press “Y” to enable tamper reporting to second central station. Enter
“N” to disable reporting.
Question 44
2CS Sys Rpt (Y/N)
Press “Y” to enable reporting of system report to second central
station. Enter “N” to disable reporting.
Question 45
2nd ID #
Enter the 4-digit customer account number for the second central
station, 0001-9999. If you answered “Y” (ECP Mode enabled) to
Question 1, you MUST enter the second customer account number
because the panel may request that a given message is to be sent to
the second central station.
Question 46
2nd City
Enter the secondary city code 2-digit ID (01-99 decimal). If you
answered “Y” (ECP Mode is enabled) to Question 1, you MUST
enter the secondary city code because the panel may request that a
given message is to be sent to the second central station.
Question 47
2nd CS ID
Enter the second central station's system ID number, 01-FE. This ID
number must be different from the one programmed in Question 4
(the Primary CS ID). If you answered “Y” (ECP Mode is enabled) to
Question 1, you MUST enter the second central station number
because the panel may request that a given message is to be sent to
the second central station. This number DOES NOT have to be
different from the primary number, in this case.