6HFWLRQ.H\ERDUG&RPPDQGV
7720P Keyboard Commands
When 7720P is plugged in, ECP communications are disabled.
“A”
7835C x.xx
(c) Pittway 1999
Software Revision
Display the installed software Revision.
“B”
NET OK -xxxDBM Z
MIN xxx-xxx-xxxx
Radio & Connectivity Display
“NET OK” indicates that the 7835C is in contact with a local cell
and AlarmNet.
“–xxxDBM” is the numeric value of the RSSI bar graph. It indicates
the power level at which the 7835C is receiving the local cell. Note:
-dBm is a measure of power; decibels less than a milliwatt. A
reading of –98DBM is a better signal than –104DBM.
“Z” = A or B carrier
“MIN xxx-xxx-xxxx” is the radio’s unique identification number
NET NS -xxxDBM Z
MIN xxx-xxx-xxxx
“NET NS” (no service) indicates the 7835C is in contact with a local
cell but has no AlarmNet service.
“Z” = A or B carrier
NO CONTACT
MIN xxx-xxx-xxxx
“NO CONTACT” indicates that the 7835C has lost contact with the
local cell and AlarmNet.
“C”
NET TIME
“NET TIME” displays the network time.
“E”
Channel = xxx
Sys=x SID=z xxxx
Network System Display
“Channel = xxx” indicates the control channel that the 7835C is
using to communicate with the local cell.
“Sys=x” indicates the local carrier (“A” side or “B” side) that the
7835C is connected with. Note that this number may be zeroes if the
7835C is in the carrier search process.
“SID=z xxxx” is the System Identification Number, the unique ID
number for each cellular carrier, where:
“z” is the international identifier code:
0 = United States
1 = other countries
2 = Canada
3 = Mexico
“xxxx” is a numeric value from 0000 – 1023
“F”
A mz xxxx
B mz xxxx PREF *
Carrier Display
* = Carrier currently selected
“xxxx” is the System Identification Number. Note that this number
may be zeroes if the 7835C is in the carrier search process.
“z” = the international identifier code where:
0 = United States
1 = other countries
2 = Canada
3 = Mexico
“M” = MicroBurst service found. Blank if not found.
“PREF” = Preferred side selected in question 7
“D”
Bat Test Start
Hit S to Chk
Battery Test
This selection initiates a 10-min. battery test. The charger is removed
from the battery and a load is applied for 10 min. The “S” command
can be used to monitor the battery condition throughout the test.